System specifications describe the physical characteristics of the Infoblox 1405 Series series appliances. Environmental specifications describe Infoblox 1405 Series series temperature and moisture limits. Power specifications describe the electrical range within which the appliance circuitry can operate. Note that the Infoblox 1405 appliance models use the CR2032 battery.
...
Caution: Infoblox recommends provisioning power according to the AC or DC power specifications listed in the specifications below.
...
...
System Specifications
- Form Factor: 1-U rack-mountable appliance
- Dimensions: 44mm H x 441 mm W x 547mm D
- Weight: Approximately 20 lbs (9.07 kg)
- Ethernet Ports: MGMT, HA, LAN1, LAN2 – auto-sensing 10Base-T/100Base-T/1000Base-T
- Serial Port: DB-9 (9600/8n1, Xon/Xoff)
- USB Port: USB 3.0
- Safety: FCC, CE, TUV, CB, VCCI, C-Tick, KCC, CCC, NOM, BIS, EAC
...
...
Environmental Specifications
- Operating Temperature: 41 to 95 degrees F (5 to 35 degrees C)
- Storage Temperature: - 40 to 122 degrees F (-40 to 50 degrees C)
- Operating Relative Humidity: 5% to 95% (non-condensing)
- Airflow CFM (Cubic Feet/Minute): 81 CFM
- Airflow Direction: Front-to-Back
- Environmental Certification: WEEE and RoHS
...
Power Specifications
- AC Power Supply: 100 to 240VAC 600W (Maximum)
- Rated Input Frequency: 50 to 60 Hz
- Rated Input Current: 7.5A at 100VAC, 3.5A at 240VAC
- Inrush Current: <25 A max at 240VAC
- Maximum Heat Output (BTU/hour): 2355 Maximum
- Power Factor: 0.98 at 100VAC/60Hz, 0.94 at 230VAC / 50Hz
- DC Power Supply: -48V 600W GRND TERM, RING, VIN 12-10 AWG #10
- Rated Input Voltage: -48VDC
- Rated Input Current: 18A max @ -44VDC, 10A max @ -65VDC
- Maximum Inrush Current: <20A
- Maximum Heat Output (BTU/hour): 2355 Maximum
...
- TE-1405-DC Base: 197w
- PT-1405-DC with Trillian LE: 222w
- TE-1405-DC with 1G Silicom: 209w
- TE-1405-DC with 10G Silicom: 224w
- ND-1405-DC Base: 232w
- ND-1405-DC 1G Silicom: 237w
- ND-1405-DC 10G Silicom: 257w
...
...
DC Power Cable Color Codes
DC power cables ship with a label describing each lead. Each label is located near the pigtail leads. Table 4 The below table lists -48V DC power specifications. Note that no color coding standards exist for DC power connections. The color coding used by the external DC power source at your site determines the color coding for the leads on the power cables that attach to the terminal studs on each DC power supply.
anchor
Cable Pin | Cable Color | Description |
---|---|---|
1 | Black | Positive Return |
2 | Red | Negative Input Voltage |
3 | Green/Yellow | Safety Ground |
Fan FRU (Field-Replaceable Unit) SKU (Stock Keeping Unit)
...